Frequently Asked Questions

2020firesydney

The Best Choice for

Testing, Maintenance and
Installation of Fire Services in Sydney.

1300 340 210

Here are some answers to the most Frequently Asked Questions.

 

  • How do I say ’20/20 Fire Protection’?  Twenty- Twenty Fire Protection! 
  • Will we have to come up with a new name in the year 2020? Our choice of 20/20 Fire Protection for our name is about 20/20 vision.   We’ve all had experience with fire companies taking compliance too far.  20/20 Fire applies 20/20 vision, takes a logical approach and ensures you get a safe property at an affordable price.
  • Who can sign my annual fire safety statement? It is the owners responsibility to provide the statement; however, the statement can be signed by anyone designated to act as an agent of the owner. 
  • What is the risk to the owner if the annual fire safety statement is wrong?  Even if the statement is signed by your fire company or agent, the responsibility for accuracy remains with the owner.  If  someone is injured in a building, the liability is first placed upon the owner until they can prove otherwise. In other words, make sure that the person signing the statement knows what they are doing and has a track record or qualification to prove it. 
  • How much does an annual fire safety statement cost?  Every building will be different, so a fixed price is impossible without an inspection. You can be sure that every piece of fire equipment and every part of the building will need to be inspected and tested, so if the price seems too good to be true, it probably is- opening the building owner and occupants to unnecessary risk.
  •  Are Smoke alarms required in all residential premises? Yes, the Smoke Alarms Act requires all new, renovated and leased premises to have a working smoke alarm. If your AFSS references BCA Spec E2.2a, the smoke alarm must also be 240 volt with battery back-up.
  • Can I fit a lock to my strata unit fire door?  Yes, but not without permission. If it’s a strata property, the strata plan, not the unit own the door and AS1905.1 (the fire door code) only allows certain modifications to the door- contact your strata manager & they will discuss it with a fire specialist
  • Why is my smoke detector going into alarm?  There are many reasons; however, the most common are false alarms (due to smoke, dirt, dust or steam ingress) or the detector getting dirty.  Smoke detectors get dirty due to a build up of dirt, dust or insects and they become more sensitive.  Smoke detectors in any environment where dust is possible should be cleaned every two years to avoid false alarm.  Regular false alarms can incur large fines from the NSW Fire Brigade.
  • How often do my fire extinguishers have to be checked? Australian Standard AS1851-2012, requires all extinguishers to be checked and tagged every six months.  Depending on the type of extinguisher, they also need an overhaul every one to five years.
  • Do I need to issue an ‘Annual Fire Safety Statement’ to council?  Yes- every building other than class 1 (house) is required to provide an annual statement to council.  This is required under the Environmental Planning and Assessment Regulation 2000